    Product parameters of the Single Cable Vertical Flammability Tester 
     Vertical burning chamber  W300xH1200xD450mm
     Gas  Use high purity propane gas or liquefied petroleum gas (provide by user-self)
     Specimen length  600±25mm
     Area of specimen  Total section area less than 0.5mm2
     Testing temperature  This device is located in a stuffiness room and the temperature keeping the 23±10℃ for testing
     Burning time  continuously setting between 0.1-999.9S, during the setting time flame could continuously burning the specimen
     Control function  Switch can choose to be manual or automatically according to the actual needed
     Gas flow range  0.1-1L/min
     Area flow range  0.1-1m3/h
     Burner  500W for standards power, 125±25mm for total height of the flame
     Temperature measurement system  according to GB/T5169.14-2007 and IEC60695-11-03 standard requirements, including temperature copper (10g), K type thermocouple and diameter is 0.5 mm with stainless steel sheathed, stopwatch and thermometer etc.
    Product information of the Single Cable Vertical Flammability Tester 

    Single Cable Combustion Tester is the most widely used and lower cost of cable fire performance test equipment, which can meet the standards IEC 60332-1-1:2004 in the provisions of technical indicators and requirements. Single cable combustion Tester is used to test the flame retardant property of the cable's insulating layer under abnormal conditions such as overheat and overcurrent. It can be used in vertical cable or fiber flame spread test, also can be test the state of flaming droplets during combustion.

    Application
    Applies to check thesingle insulation wire and cable vertical spreading test which total section area less than 0.5mm2
    Standards
    According to IEC60332-1-1:2004, IEC60332-1-2:2004,  IEC60332-1-3:2004, EN50265-1, EN50265-2-1